GGooseAtlas
BetaPatented methodCanada and the Caribbean

How much of this was the weather?

Send your bills and a location. We add the weather that actually occurred over each billing period, separate the load that responds to it from the load that does not, and return what the site would have used in normal weather.

Stations
8,803
From
1840
Current to
2026-11-23
With 1991-2020 normals
1,852

A worked example

Station 7637 TORONTO CITY, 2 km away · 24 billing periods · normalized to 9.71 degC

Actually used
1,039 MWh
24 periods
At normal weather
1,114 MWh
at 9.71 degC
Weather effect
+7.14%
74,239 kWh
Model fit
r² 0.96
linear, above baseload

Where the energy went, period by period

030k60k90kkWhheating peakcooling peakJanAprJulOctJanAprJulOct20232024
Passive baseloadActive baseloadHeatingCooling

The weather that produced that shape

250-5degC-1.2 degC23 degC2023-01 mean -1.2 degC · 595 HDD · 0 CDD2023-02 mean 1.1 degC · 474 HDD · 0 CDD2023-03 mean 3.1 degC · 462 HDD · 0 CDD2023-04 mean 10.7 degC · 226 HDD · 9 CDD2023-05 mean 16.7 degC · 76 HDD · 35 CDD2023-06 mean 20.8 degC · 10 HDD · 95 CDD2023-07 mean 22.1 degC · 0 HDD · 127 CDD2023-08 mean 21.1 degC · 3 HDD · 99 CDD2023-09 mean 18 degC · 29 HDD · 30 CDD2023-10 mean 10 degC · 250 HDD · 1 CDD2023-11 mean 3.8 degC · 425 HDD · 0 CDD2023-12 mean 2.7 degC · 474 HDD · 0 CDD2024-01 mean -0.6 degC · 575 HDD · 0 CDD2024-02 mean 2.9 degC · 439 HDD · 0 CDD2024-03 mean 4.4 degC · 421 HDD · 0 CDD2024-04 mean 11.4 degC · 198 HDD · 0 CDD2024-05 mean 18.1 degC · 35 HDD · 37 CDD2024-06 mean 21.3 degC · 11 HDD · 109 CDD2024-07 mean 23 degC · 0 HDD · 156 CDD2024-08 mean 20.1 degC · 17 HDD · 83 CDD2024-09 mean 18.9 degC · 24 HDD · 51 CDD2024-10 mean 11.7 degC · 196 HDD · 2 CDD2024-11 mean 4.4 degC · 408 HDD · 0 CDD2024-12 mean -0.4 degC · 570 HDD · 0 CDD
Across 24 periods the site used 1,039,485 kWh. At a steady 9.7 degC it would have used about 1,113,724 kWh, 74,239 kWh more (7.1%).
The site uses at least 11,742 kWh in every period whatever the weather does. With no heating and no cooling at all it would use about 13,807 kWh, the 2,065 kWh difference being load that follows occupancy and operation.

Real weather, generated building. The station, the meter-read windows and the degree days come out of the archive. The consumption is a synthetic 4,200 m² office, because we are not publishing a client’s bills. Everything after that, including those two sentences, is what the API returned.

What it does, in order

  1. 01

    Validate what arrived

    Bad periods are reported, never dropped in silence.

  2. 02

    Add the weather that occurred

    Daily temperatures summed over your real meter-read window.

  3. 03

    Split the load

    Passive baseload, active baseload, heating, cooling.

  4. 04

    Fit the weather model

    On consumption above the baseload, linear or neural.

  5. 05

    Re-evaluate at normal weather

    Your series mean, the WMO normal, or a temperature you pick.

  6. 06

    The method is patented

    CA 2,996,731 C and US 10,770,898 B2, Screaming Power Inc., who also run this archive.

▸Why each step is done that way

01 · Validate what arrived

Periods with no energy, negative readings or missing weather are reported, not dropped silently. Points far from the rest of the series are flagged by modified z-score and kept in the model, because a meter rollover and a genuinely cold January look identical to a statistic and deleting the second one would quietly change your answer.

02 · Add the weather that occurred

The nearest station that is genuinely reporting over your dates, then daily temperatures summed over your real meter-read window. A billing period is not a calendar month, and degree days computed from a period mean rather than summed daily is the most common way a normalization goes wrong before it starts.

03 · Split the load

Only the part that moves with weather can be normalized; the baseload is the part that does not. Normalizing without separating them moves the baseload around with the temperature, which is how a normalization finds a saving in a building where nothing changed.

04 · Fit the weather model

A linear fit, or a neural network where there is enough history, on consumption above the baseload only. Temperature, wind, solar radiation, humidity and occupancy where you track it. The coefficients come back with what each one indicates: temperature reads as mass and insulation, wind as air leakage, solar as glazing.

05 · Re-evaluate at normal weather

The same fitted model, with the temperature replaced by the normalization temperature and everything else left as it was. Normalize to your own series mean, to this station's WMO 1991-2020 climate normal, or to a temperature you choose.

Three endpoints, one body

The same consumption series answers three different questions. Send it once in whichever shape you hold it.

POST /api/v2/normalize

Normalize

How much of this was the weather?

  • normalized total
  • weather effect
  • the load split
  • the fitted model
▸ Show the request
curl -X POST https://gooseatlas.ca/api/v2/normalize \
  -H "Authorization: Bearer YOUR_KEY" -H "Content-Type: application/json" \
  -d '{
    "location": { "lat": 43.6532, "lon": -79.3832 },
    "periods": [
      { "period": "2024-01", "from": "2024-01-09", "to": "2024-02-07",
        "electricKwh": 42100, "gasM3": 9800 }
    ],
    "options": { "normalizeTo": "climate", "floorAreaM2": 4200 }
  }'

# Send from and to. They are the meter-read dates, and the weather is summed
# over that window. Omit them and we assume the calendar month and say so.
POST /api/v2/profile

Profile

When it is used, and in what shape.

  • peak and base demand
  • load factor
  • weekday and weekend shapes
  • hour by weekday heat map
  • the turning temperature
▸ Show the request
curl -X POST https://gooseatlas.ca/api/v2/profile \
  -H "Authorization: Bearer YOUR_KEY" -H "Content-Type: application/json" \
  -d '{ "unit": "kWh",
        "location": { "lat": 43.6532, "lon": -79.3832 },
        "readings": [ { "t": "2024-01-01T00:00:00Z", "v": 12.4 }, ... ] }'

# The change point is fitted separately for weekdays and weekends. One line
# through both finds a temperature that belongs to neither.
POST /api/v2/benchmark

Benchmark

How accurate is it, and how does the building compare?

  • nine models scored out of sample
  • CV(RMSE) and NMBE
  • savings uncertainty
  • NRCan intensities
▸ Show the request
curl -X POST https://gooseatlas.ca/api/v2/benchmark \
  -H "Authorization: Bearer YOUR_KEY" -H "Content-Type: application/json" \
  -d '{ "location": { "lat": 43.6532, "lon": -79.3832 },
        "periods": [ ... the same bills ... ],
        "options": { "floorAreaM2": 4200 },
        "building": { "activity": "office", "yearBuilt": 1988, "hoursPerWeek": 60 } }'

Every response carries quality: each period dropped and why, each outlier flagged, each warning about the fit. A result you cannot interrogate is not worth having.

Ask it to prove it

A normalization that reports no accuracy is an opinion. The benchmark will tell you when our method is not the best one for your site, because a benchmark that cannot say that is marketing.

Nine models, same history

A flat mean, a line on temperature, degree-day regressions, the three-, four- and five-parameter change-point models of ASHRAE RP-1050, and both forms of ours. Every one refits inside every fold, the load split included, so nothing is marked on a paper it has already read.

Scored out of sample

CV(RMSE) and NMBE against ASHRAE Guideline 14, a harder test that fits the earlier periods and predicts the later ones, and the uncertainty that would attach to a measured saving.

Against real buildings

Normalized intensity beside NRCan’s published figures, by type, size, vintage, operating hours and climate zone. Those are 2009 means, not medians, and the comparison says so every time.

Two models that cannot be told apart are not ranked

Thirty noisy periods are enough for a weather model to beat a flat average by a tenth of a point purely by chance. So the model chosen is the simplest one within one standard error of the lowest, not whichever came first on the list. Both numbers come back, and the response says which was chosen and why.

▸What this is built on
  • ASHRAE Guideline 14 - Measurement of Energy, Demand, and Water Savings. The acceptance criteria and the savings-uncertainty expression.
  • ASHRAE RP-1050 - Kissock, Haberl and Claridge, the Inverse Modeling Toolkit: the change-point models we are compared against, and the change-point search.
  • PRISM - Fels, Energy and Buildings, 1986. Degree-day regression on utility bills as a measurement rather than an estimate.
  • Reddy and Claridge - Uncertainty of “measured” energy savings from statistical baseline models, HVAC&R Research 6(1), 2000.
  • Sun and Baltazar - The reporting-length factor in the savings uncertainty, ASHRAE Transactions, 2013.
  • CalTRACK Methods 2.0 - Section 4.3.2.4, for the form of the fractional savings uncertainty used here.
  • Granderson and others, LBNL - Evaluation of Methods to Assess the Uncertainty in Estimated Energy Savings: why a baseline is tested out of sample.
  • Hastie, Tibshirani and Friedman - The Elements of Statistical Learning, section 7.10: the one-standard-error rule for choosing between models.
  • NRCan - Survey of Commercial and Institutional Energy Use, Buildings 2009, and the Comprehensive Energy Use Database: the published intensities.
  • CA 2,996,731 C / US 10,770,898 B2 - Screaming Power Inc. The normalization method itself.

What it will not do

✕ Three months of bills

The model needs a heating and a cooling season. Twelve months is the floor, and it says so instead of returning a confident number.

✕ Calling it a saving

Normalization says what the weather cost or saved. Whether the rest is a saving depends on what else changed at the site.

✕ Hiding a poor fit

Where the model explains little of the variation it says so in plain words, and the r-squared is in the response.

✕ Inventing weather

Where a station is missing days, the days found against days requested come back for every period.

Talk to us about it

Beta means we would rather hear what you need than guess. Tell us what data you hold and what you are trying to compare, and we will tell you honestly whether this helps.

We will use this to reply to you. Nothing else.