A worked example
Station 7637 TORONTO CITY, 2 km away · 24 billing periods · normalized to 9.71 degC
Where the energy went, period by period
The weather that produced that shape
Real weather, generated building. The station, the meter-read windows and the degree days come out of the archive. The consumption is a synthetic 4,200 m² office, because we are not publishing a client’s bills. Everything after that, including those two sentences, is what the API returned.
What it does, in order
- 01
Validate what arrived
Bad periods are reported, never dropped in silence.
- 02
Add the weather that occurred
Daily temperatures summed over your real meter-read window.
- 03
Split the load
Passive baseload, active baseload, heating, cooling.
- 04
Fit the weather model
On consumption above the baseload, linear or neural.
- 05
Re-evaluate at normal weather
Your series mean, the WMO normal, or a temperature you pick.
- 06
The method is patented
CA 2,996,731 C and US 10,770,898 B2, Screaming Power Inc., who also run this archive.
▸Why each step is done that way
01 · Validate what arrived
Periods with no energy, negative readings or missing weather are reported, not dropped silently. Points far from the rest of the series are flagged by modified z-score and kept in the model, because a meter rollover and a genuinely cold January look identical to a statistic and deleting the second one would quietly change your answer.
02 · Add the weather that occurred
The nearest station that is genuinely reporting over your dates, then daily temperatures summed over your real meter-read window. A billing period is not a calendar month, and degree days computed from a period mean rather than summed daily is the most common way a normalization goes wrong before it starts.
03 · Split the load
Only the part that moves with weather can be normalized; the baseload is the part that does not. Normalizing without separating them moves the baseload around with the temperature, which is how a normalization finds a saving in a building where nothing changed.
04 · Fit the weather model
A linear fit, or a neural network where there is enough history, on consumption above the baseload only. Temperature, wind, solar radiation, humidity and occupancy where you track it. The coefficients come back with what each one indicates: temperature reads as mass and insulation, wind as air leakage, solar as glazing.
05 · Re-evaluate at normal weather
The same fitted model, with the temperature replaced by the normalization temperature and everything else left as it was. Normalize to your own series mean, to this station's WMO 1991-2020 climate normal, or to a temperature you choose.
Three endpoints, one body
The same consumption series answers three different questions. Send it once in whichever shape you hold it.
POST /api/v2/normalizeNormalize
How much of this was the weather?
- normalized total
- weather effect
- the load split
- the fitted model
▸ Show the request
curl -X POST https://gooseatlas.ca/api/v2/normalize \
-H "Authorization: Bearer YOUR_KEY" -H "Content-Type: application/json" \
-d '{
"location": { "lat": 43.6532, "lon": -79.3832 },
"periods": [
{ "period": "2024-01", "from": "2024-01-09", "to": "2024-02-07",
"electricKwh": 42100, "gasM3": 9800 }
],
"options": { "normalizeTo": "climate", "floorAreaM2": 4200 }
}'
# Send from and to. They are the meter-read dates, and the weather is summed
# over that window. Omit them and we assume the calendar month and say so.POST /api/v2/profileProfile
When it is used, and in what shape.
- peak and base demand
- load factor
- weekday and weekend shapes
- hour by weekday heat map
- the turning temperature
▸ Show the request
curl -X POST https://gooseatlas.ca/api/v2/profile \
-H "Authorization: Bearer YOUR_KEY" -H "Content-Type: application/json" \
-d '{ "unit": "kWh",
"location": { "lat": 43.6532, "lon": -79.3832 },
"readings": [ { "t": "2024-01-01T00:00:00Z", "v": 12.4 }, ... ] }'
# The change point is fitted separately for weekdays and weekends. One line
# through both finds a temperature that belongs to neither.POST /api/v2/benchmarkBenchmark
How accurate is it, and how does the building compare?
- nine models scored out of sample
- CV(RMSE) and NMBE
- savings uncertainty
- NRCan intensities
▸ Show the request
curl -X POST https://gooseatlas.ca/api/v2/benchmark \
-H "Authorization: Bearer YOUR_KEY" -H "Content-Type: application/json" \
-d '{ "location": { "lat": 43.6532, "lon": -79.3832 },
"periods": [ ... the same bills ... ],
"options": { "floorAreaM2": 4200 },
"building": { "activity": "office", "yearBuilt": 1988, "hoursPerWeek": 60 } }'Every response carries quality: each period dropped and why, each outlier flagged, each warning about the fit. A result you cannot interrogate is not worth having.
Ask it to prove it
A normalization that reports no accuracy is an opinion. The benchmark will tell you when our method is not the best one for your site, because a benchmark that cannot say that is marketing.
Nine models, same history
A flat mean, a line on temperature, degree-day regressions, the three-, four- and five-parameter change-point models of ASHRAE RP-1050, and both forms of ours. Every one refits inside every fold, the load split included, so nothing is marked on a paper it has already read.
Scored out of sample
CV(RMSE) and NMBE against ASHRAE Guideline 14, a harder test that fits the earlier periods and predicts the later ones, and the uncertainty that would attach to a measured saving.
Against real buildings
Normalized intensity beside NRCan’s published figures, by type, size, vintage, operating hours and climate zone. Those are 2009 means, not medians, and the comparison says so every time.
Two models that cannot be told apart are not ranked
Thirty noisy periods are enough for a weather model to beat a flat average by a tenth of a point purely by chance. So the model chosen is the simplest one within one standard error of the lowest, not whichever came first on the list. Both numbers come back, and the response says which was chosen and why.
▸What this is built on
- ASHRAE Guideline 14 - Measurement of Energy, Demand, and Water Savings. The acceptance criteria and the savings-uncertainty expression.
- ASHRAE RP-1050 - Kissock, Haberl and Claridge, the Inverse Modeling Toolkit: the change-point models we are compared against, and the change-point search.
- PRISM - Fels, Energy and Buildings, 1986. Degree-day regression on utility bills as a measurement rather than an estimate.
- Reddy and Claridge - Uncertainty of “measured” energy savings from statistical baseline models, HVAC&R Research 6(1), 2000.
- Sun and Baltazar - The reporting-length factor in the savings uncertainty, ASHRAE Transactions, 2013.
- CalTRACK Methods 2.0 - Section 4.3.2.4, for the form of the fractional savings uncertainty used here.
- Granderson and others, LBNL - Evaluation of Methods to Assess the Uncertainty in Estimated Energy Savings: why a baseline is tested out of sample.
- Hastie, Tibshirani and Friedman - The Elements of Statistical Learning, section 7.10: the one-standard-error rule for choosing between models.
- NRCan - Survey of Commercial and Institutional Energy Use, Buildings 2009, and the Comprehensive Energy Use Database: the published intensities.
- CA 2,996,731 C / US 10,770,898 B2 - Screaming Power Inc. The normalization method itself.
What it will not do
✕ Three months of bills
The model needs a heating and a cooling season. Twelve months is the floor, and it says so instead of returning a confident number.
✕ Calling it a saving
Normalization says what the weather cost or saved. Whether the rest is a saving depends on what else changed at the site.
✕ Hiding a poor fit
Where the model explains little of the variation it says so in plain words, and the r-squared is in the response.
✕ Inventing weather
Where a station is missing days, the days found against days requested come back for every period.
Talk to us about it
Beta means we would rather hear what you need than guess. Tell us what data you hold and what you are trying to compare, and we will tell you honestly whether this helps.